Sizing solar plus battery: the questions that decide the design and the cost

A battery is not just a bigger solar panel. It is a separate machine with its own job, and that job decides its size, cost and how it is controlled.

In this article
  1. Question 1: What is the battery for?
  2. Question 2: Which loads must stay on?
  3. Three terms, explained
  4. Question 3: How much energy and how much power?
  5. Question 4: How is the solar array sized?
  6. What each hour of backup costs
  7. Why solar alone does not keep the lights on
  8. Question 5: Which battery and which inverter?
  9. Question 6: What does the control strategy do?
  10. When a battery pays for itself: the diesel case
  11. Three designs, side by side
  12. Battery life and the replacement budget
  13. The sizing sheet to ask for
  14. Common mistakes
  15. How AVEX GRID helps

Key points

  • Decide the job first: backup during power cuts, using solar in the evening, cutting peak demand, or a mix.
  • A battery has two sizes: energy (kWh) for how long it can supply, and power (kW) for how much it can supply at once.
  • At about US$320 per kWh, each hour of backup for a 15 kW load costs about US$6,000. Ask how long your power cuts really last.
  • Compared with running a diesel generator, the whole solar-plus-battery package paid back in about 1.6 years in our example.
  • You rarely need every load running through every power cut. A modest battery with sensible priorities is usually the cheapest answer.

A hybrid system combines solar panels, a battery, and the grid or a generator. The setup that suits a clinic is different from the one that suits a cold store or a mine camp. This article explains the questions an engineer asks. We list them in the order in which the answers shape the design.

Question 1: What is the battery for?

PurposeWhat it needs
Backup during power cutsPower for the critical loads, and energy for the length of a typical power cut
Evening supplyEnergy to carry the solar power into the hours after sunset
Peak shavingHigh power for short periods, with modest energy. This cuts your highest demand
Less generator useEnergy and power to cover the loads the generator would carry

One battery can serve more than one purpose, but each purpose adds a requirement. So name your first priority. Otherwise you may get a system that is large and expensive and still fails at the one job that matters.

Question 2: Which loads must stay on?

List every load and mark it as critical, important or flexible. A clinic's vaccine fridge and theatre lights are critical. A water pump is flexible, because it can run when the sun is high. This list is the most important input to the design. It cuts the battery size more than any change to the equipment.

Three terms, explained

Batteries are described by two numbers that are easy to confuse. Energy (kWh) sets how long the battery can supply a load. Power (kW) sets how large a load it can supply at once. A datasheet adds a few more terms.

TermIn plain wordsWhy it matters to you
Usable capacityThe kWh you can really drawSize from this, not from the label
C-rateHow fast it can deliverA big load needs a battery that can supply that power
Round-trip efficiencyWhat you get backAbout 90% for lithium. Plan on it

Recharging sets the size of the solar array. To refill the battery in one day, the array must make the battery's usable energy, plus the losses, from a day's yield of about 4.5 kWh per kWp.

Worked exampleTo refill 60 kWh of usable energy at 90% round-trip efficiency, with a yield of 4.5 kWh per kWp a day, you need about 60 ÷ (0.9 × 4.5) = 14.7 kWp of solar, on top of what the daytime load uses.

Question 3: How much energy and how much power?

The energy you need is the critical load multiplied by the hours it must run on battery. The power you need is the highest critical load running at one time. This includes the surge when motors start.

Worked exampleA site has a critical load of 15 kW and wants four hours of backup. That needs 60 kWh of usable energy. You may use only 80% of the battery's rating. So the nameplate size is 60 divided by 0.8, which is 75 kWh. The inverter must support 15 kW continuously, plus any starting surge.
Battery energy needed to carry a 20 kW critical loadNominal battery size in kWh, using 90% of capacity
050100150200133 kWh178 kWh2 h4 h6 h8 hOutage length the battery must cover, hours

Calculated as load times hours divided by 0.9. Losses and ageing add margin; the real design uses an hourly model. Source: AVEX GRID calculation.

Question 4: How is the solar array sized?

The array has two jobs. It must supply the daytime load and recharge the battery. Say you want the battery full by the afternoon after a full discharge. Then the array must produce enough extra power over the day to refill it. If the extra power is too little, the battery is only partly charged when the next power cut starts.

kWhenergy: how long the battery can supply a load
kWpower: how much the battery and inverter can supply at once
DoDdepth of discharge: the share of the rated energy that you may use

What each hour of backup costs

Go back to the worked example: a 15 kW critical load, with a battery you may discharge to 80% of its rating. Each hour of backup needs 15 kWh of usable energy, which is 18.75 kWh of nameplate. The calculator's rough default for battery cost is US$320 per kWh installed. At that price, one hour of backup costs about US$6,000 of battery. The cost rises in a straight line. So ask yourself: is the last hour worth it?

Battery cost against hours of backupUS dollars for a 15 kW critical load, 80% usable, US$320 per kWh installed
US$6,000
1 hour
US$12,000
2 hours
US$24,000
4 hours
US$36,000
6 hours
US$48,000
8 hours

Battery only; the inverter, protection and installation are extra. The US$320 per kWh figure is the calculator’s indicative default. Source: AVEX GRID calculation

Most sites find that the first two or three hours give most of the value, because most power cuts are short. The hours beyond that are better handled by a generator that starts only when it is needed. The honest design question is how long your power cuts really are, not how long they could be. Keep a log of the dates and lengths of power cuts over the past year. Your own records or ZETDC notices can supply it. This turns a guess into a number.

Recharging is part of the sizeA battery that cannot refill works only once. To restore 60 kWh of usable energy at about 90% round-trip efficiency, the array must deliver roughly 67 kWh over the day, beyond what the load uses. The average yield is 4.5 kWh per kWp per day, from 1,650 kWh per kWp a year. So you need about 15 kWp of extra capacity. In the weakest month you need more, so design for that month.

Why solar alone does not keep the lights on

Many people are surprised by this. A grid-tied solar plant with no battery switches off the moment the grid fails. This is a safety rule called anti-islanding. It protects line workers from power coming back into the line from your roof. If you need power during a power cut, you need a battery or a generator. You also need an inverter that can make its own supply. This is the difference between a system that only saves money and one that also protects your operations. Settle it with your supplier first.

Question 5: Which battery and which inverter?

  • Chemistry. Lithium iron phosphate is widely used because it lasts many cycles and is safer. The choice also depends on the operating temperature, the warranty and whether service is available.
  • Cycle life and warranty. A battery that charges and discharges daily needs a warranty stated in cycles and in years. Check the conditions attached.
  • Inverter type. Hybrid and battery inverters differ in power rating, surge capacity and how they connect to a generator or the grid.
  • Protection and monitoring. Correct fuses, earthing, ventilation and remote monitoring protect people and your investment.

Question 6: What does the control strategy do?

A controller decides when the battery charges and discharges. It also decides when the grid or generator steps in. A simple rule keeps a reserve for power cuts and uses the rest for daily savings. The rules are written down and tested when the system is commissioned. This makes sure the system behaves as designed.

When a battery pays for itself: the diesel case

Backup is insurance. A battery also earns its keep when it replaces diesel. The calculator's diesel case takes a site with a 180 kW load. A generator runs it 6 hours a day for 300 days a year. The generator burns 98,182 litres and delivers energy at about US$0.64 per kWh. This uses the diesel price at the October 2026 ZERA maximum of US$2.04 a litre. Now add solar and a battery to cover 40% of that energy. The picture changes.

Value
Solar array87 kWp, US$82,935
Battery144 kWh, US$46,080
Total investmentUS$129,015
Generator energy replaced129,600 kWh a year
Diesel avoided39,273 litres a year
Saving a yearUS$81,418
Simple payback1.6 years
36%of this investment is the battery; the rest is the solar array
39,273 Lof diesel avoided a year in this case
1.6 yrssimple payback, because generator energy is expensive to replace

This is why a battery next to a generator is easier to justify than a battery next to a cheap grid connection. Generator energy is expensive, so replacing it saves a lot. Our guide to cutting diesel cost shows how to measure that cost first. Treat the numbers as a guide. The hourly model and your own prices decide the real result.

Three designs, side by side

SiteBattery jobSizing driverWhere the generator fits
ClinicKeep the vaccine fridges, theatre and lights runningCritical load and length of power cutsA last-resort backup for long power cuts
Cold store or packhouseCarry the compressors through short cuts, and move solar power into the eveningCompressor starting current, and how long the room holds its coldOn standby, started by the controller
Day-shift factoryCut the peak and ride through power cutsPeak power, not energyRarely needed if the battery carries the load

Battery life and the replacement budget

The battery is the part of a hybrid system that wears out with time. Cells age with use, deep discharge and heat. Many lithium iron phosphate products are rated at several thousand cycles. But the rating applies only under stated conditions. So read the warranty for the number of cycles, the capacity it guarantees at the end of life, and the temperature range it assumes. In your financial model, include a battery replacement part-way through the life of the plant, at a lower price than today. Show the result with and without it. A model that leaves out replacement makes the payback look better than it is.

The sizing sheet to ask for

  1. The load list, with each load marked critical, important or flexible.
  2. The power-cut record the design assumes: how often and how long.
  3. Usable and nameplate battery energy, and the depth of discharge assumed.
  4. Inverter continuous and surge power, with the motor starting current checked.
  5. The array size, and the weakest month in which it still recharges the battery.
  6. The control rules: reserve level, when the generator starts and stops, and charging priority.
  7. The cycle life and warranty conditions of the battery.
  8. Protection, ventilation, access and fire safety.

The rules for the solar part are in own-consumption solar and net metering, and the economics of the array alone are in is solar worth it for your factory.

Common mistakes

  • Sizing the battery on the whole site load instead of the critical load.
  • Forgetting the motor starting current when sizing the inverter.
  • Buying a battery whose usable energy is well below the number on the label.
  • Installing without a plan for ventilation, access and fire protection.

How AVEX GRID helps

  • Load priority review and measured profiles, so the battery size rests on data.
  • System design with single-line diagrams, protection and control rules.
  • Commissioning and verification so the system performs as specified.

What AVEX GRID can take off your hands

AVEX GRID is an engineer-led energy consultancy in Zimbabwe. We do the technical work that turns an energy investment into a plant that is licensed, connected, financed and performing, whether you are a local operator or an investor overseas.

Feasibility and bankable studiesYield, load and hybrid models, and the technical file lenders and ZERA read.
Power-system engineering (ETAP)Load flow, short circuit, arc flash and protection studies for approvals and safe design.
Licence and PPA technical supportZERA licence documents, ZETDC connection studies, PPA technical schedules.
Owner's engineerDesign review, testing and commissioning on your side of the EPC table.
Tariff, audit and compliance workMaximum-demand and power-factor savings, readiness for energy-management rules.
Remote plus on the groundModelling for overseas teams, with an engineer in Zimbabwe for site, utility and regulator work.

We quote fixed prices after a free scoping call and reply the same working day.

Frequently asked questions

How do I decide how many hours of backup to buy?

Start from the real power-cut record for your site, not the worst case you can imagine. Most power cuts are short. So the first hours give most of the value, and a generator can cover the rare long ones.

Do I need to replace the battery during the life of the plant?

Usually yes. Cells age with use, deep discharge and heat. Read the warranty for cycles and end-of-life capacity. Include a replacement in your financial model.

How long will a battery last in a power cut?

Divide the usable energy by the load. A battery with 60 kWh usable supplies a 15 kW load for about four hours. Real systems have losses, so the design adds a margin.

Can I run an air conditioner or a large motor on battery?

Yes, if the inverter and battery are sized for the running load and the starting surge. Motors need special care.

Does a bigger battery always cost more to run?

No. A battery has no fuel cost, but it has a limited number of cycles. So a larger battery that is discharged less deeply can last longer.

Can I add a battery later?

Often yes, if the inverter and the design allow it. It is cheaper to plan for growth at the start.

Topics: solar and battery sizinghybrid solar system Zimbabwebattery energy storageload shedding backup solardepth of dischargeinverter sizinghybrid microgrid designenergy consultant Zimbabwe

Sources and notes

General information to help you plan. The rules that apply to your site are confirmed by AVEX GRID against the current gazetted text, ZERA and ZETDC as part of the work. The sources used are listed below.

DJ

Devine Tafara Javangwe is the founder and lead consulting engineer at AVEX GRID. He holds an MSc in Electrical Power Engineering (Southern Federal University, 2025), is a Professional Member of the Zimbabwe Institution of Engineers and an IEEE member.

About the practice · Contact

Size the battery on your loads, not on a brochure.

Send us a list of your loads and your outage pattern. We return a sized design with the energy, the power and the control logic.

+263 78 488 9775 · Autherstone Street 21, Marondera, Zimbabwe · Remote across Southern Africa